Products and Services
Vacuum-Jacketed Pipe and Flexible Lines
Rigid (VIP) and flexible (VIF) vacuum insulated lines that carry cryogenic liquids such as LN2, LOX, LAr, LNG and LCO₂ from the tank to the point of use with minimal heat loss: project-specific design, fabrication with our manufacturing partners, site installation and testing.
Request a quote and technical sheetor call: Marmara & Aegean +90 533 300 63 67 · Anatolia +90 536 433 56 44



Product range
Rigid vacuum-jacketed pipe (VIP)
- Spools from Ø12 to DN200
- Straight and field-fit spools, 45°/90°/custom bends
- Equal and reducing tees, expansion loops and bellows
- Valve boxes and instrument branches
Vacuum insulated flexible line (VIF)
- Where rigid spools are not feasible or for moving connections
- Corrugated stainless inner and outer hose, steel braiding, MLI
- Options with single bend radius from 150 mm
- Mobile tank and bulk tank filling, connection to vibrating equipment
Connection types
- Bayonet coupling: fast, weld-free assembly and disassembly
- Welded coupling (vacuum or perlite): joined by welding on site
- Flexible line ends: weld-on, UNF fitting, nipple, 3-piece union, filling lance
- Universal end: weld prep for any fitting
Main dimensions and performance
| Size | Inner pipe (Ø × t) | Outer jacket (Ø × t) | Heat loss (W/m) | Capacity (L/h)¹ |
|---|---|---|---|---|
| Ø12 | 12 × 1 mm | 33.4 × 1.65 mm | 0.5 | 245 |
| DN15 | 21.3 × 1 mm | 60.3 × 2.7 mm | 0.6 | 1,169 |
| DN25 | 33.4 × 2 mm | 76.1 × 3.05 mm | 0.9 | 2,288 |
| DN40 | 48.3 × 2.7 mm | 88.9 × 3.05 mm | 1.1 | 5,004 |
| DN50 | 60.3 × 2.7 mm | 114.3 × 3.05 mm | 1.4 | 8,020 |
| DN65 | 76.1 × 3.05 mm | 133 × 3 mm | 1.6 | 12,787 |
| DN80 | 88.9 × 3.05 mm | 141.3 × 3.4 mm | 1.8 | 17,731 |
| DN100 | 114.3 × 3.05 mm | 168.3 × 3.4 mm | 2.2 | 26,760 |
| DN150 | 168.3 × 3.4 mm | 219.1 × 3.7 mm | 3.2 | 64,796 |
| DN200 | 219.1 × 3.7 mm | 273.1 × 4.19 mm | 3.8 | 99,737 |
¹ Based on saturated boiling liquid at 1 m/s. Calculations assume an ambient temperature of 20 °C. Flexible (VIF) versions are produced to order across this range. Other sizes and pressure classes on request.
Design, materials and testing
- Standards
- PED compliant · AD2000 / EN 13480 / ASME B31.3 (others on request)
- Insulation
- Static high vacuum with MLI (≤10⁻⁴ mbar)
- Design temperature
- −196 °C / +80 °C
- Process pipe
- 1.4301 / 1.4306 / 1.4307 (≈304 / 304L)
- Vacuum jacket
- 1.4301 / 1.4307, optional 1.4404 (≈316L)
- Strength
- Dimensional check and pressure test
- NDT
- Radiography (RT) or penetrant testing (PT), visual inspection
- Leak tightness
- Helium leak test, < 1×10⁻⁹ mbar·L/s
Maintenance and vacuum restoration
As vacuum degrades over time, heat loss rises and the jacket surface starts sweating and frosting. We measure the vacuum level of existing lines and, where needed, re-evacuate them to restore performance.
Applications
- Hospital and laboratory LN2 lines
- Cryobanks and biobanks
- Industrial gas filling plants
- Food freezing and chilling
- LNG and LCO₂ facilities
- Test and R&D facilities
Let’s design your line together
Share the fluid, flow rate, routing and points of use; we will come back with a technical sheet and a quotation. You can also reach us by phone or WhatsApp.